12KVA SolidState Frequency Converter Specifications 400Hz
|
|||||
|
Model |
12KSS60400/50400 | ||||
|
Capacity |
12KVA/8.4KW | ||||
|
Electrical Input | |||||
|
Voltage |
220V -15%/+20% *see note | ||||
|
Frequency |
50Hz or 60Hz ±5% | ||||
|
Electrical Output | |||||
|
Voltage |
120Vac self-regulated 100A | ||||
|
Frequency |
400Hz | ||||
|
Voltage Regulation |
±1% | ||||
|
Frequency Stability |
±0.016Hz (Xtal oscillator) | ||||
|
Transient Response |
±3%
(100% load variation.) | ||||
|
Waveform |
Sinewave THD <3% at 0-100% linear load | ||||
|
Overload Capacity |
110% continuous,110-150% load 30 seconds, over 150% causes unit to shut down. Auto restart upon removal of the overload. | ||||
|
Power Factor |
0.8 | ||||
|
Crest Ratio |
3:1 | ||||
|
Efficiency | |||||
|
AC to AC |
>85% | ||||
|
Protection | |||||
|
Overload |
150% 30Sec cutoff (Current Limited) | ||||
|
Short Circuit |
Unit will cut off and must be manually restarted | ||||
|
EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at 70dB | ||||
|
Audible Alarm | |||||
|
Overload |
Sounds continuously | ||||
|
Fault |
Sounds continuously | ||||
|
Indicator | |||||
|
LCD |
Converter status, O/P voltage, O/P frequency, O/P Power | ||||
|
LED |
| ||||
|
Environment | |||||
|
OperationTemp. |
-10-50%ºC; 14-122ºF | ||||
|
Relative Humidity |
20-90% non-condensing | ||||
|
Audible Noise |
Less than 72dB (at 1 meter) | ||||
|
Physical | |||||
|
Input |
Terminal Block | ||||
|
Output |
Terminal Block (Worldwide outlets available) | ||||
|
Net Weight |
366lbs/166.4kg | ||||
|
Width |
18.9in/48cm | ||||
|
Depth |
13.6in/34.5cm | ||||
|
Height |
34in/86.4cm | ||||
|
Note: Input voltages of 208V single phase (phase-to-phase on a 3-phase 120/208V line)- with 2 hot lines and 240V single phase (from a 120/20V split-phase source) - 2 hot lines are both acceptable with one hot on the input N ternimal, and another hot on the L2 input terminal. | |||||
1Specifications subject to change without notice.