Specifications 400Hz
|
|||||
|
Model | |||||
|
Capacity |
1KVA/700W | ||||
|
Input | |||||
|
Voltage |
120V or 220V Input requirement 15A@120V 8.2A@220V | ||||
|
VoltageRange |
120V -15%/+20% or 220V -15%/+20% | ||||
|
Frequency |
50Hz or 60Hz | ||||
|
Phase |
Single | ||||
|
Output | |||||
|
Voltage |
120V ±20% | ||||
|
Voltage Regulation |
±1% | ||||
|
Frequency |
400Hz | ||||
|
Frequency Regulation |
±0.016Hz (Xtal oscillator) | ||||
|
Harmonic Distortion |
<3% at 100% linear load | ||||
|
Output Waveform |
Pure Sinewave | ||||
|
Output Current @.7pf |
120V-8.3A, 220V-4.6A | ||||
|
Non-linear Peak Current |
120V-12.4A, 220V-6.7A for 30 sec. | ||||
|
Power Factor |
0.7 | ||||
|
Efficiency | |||||
|
AC to AC |
>85% | ||||
|
Overload Capacity |
110% continuous,110-150% load 30 seconds, over 150% causes unit to shut down. Auto restart upon removal of the overload. | ||||
|
Short Circuit |
Unit will cut off and must be manually restarted | ||||
|
EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at 70dB | ||||
|
Over Temperature |
Inverter auto cut-off when heat sink temp over 80ºC | ||||
|
Audible Alarm | |||||
|
Overload |
Sounds continuously | ||||
|
Converter Fault |
Sounds continuously | ||||
|
Indicator | |||||
|
LCD |
Converter status, Input & Output voltage - frequency, loading % | ||||
|
LED |
| ||||
|
Environment | |||||
|
OperationTemp. |
-10-50%ºC; 14-122ºF | ||||
|
Relative Humidity |
20-90% non-condensing | ||||
|
Audible Noise |
Less than 45dB (at 1 meter) | ||||
|
Physical | |||||
|
Net Weight |
144lbs/64.8kg | ||||
|
Width |
7 1/8in/18.1cm | ||||
|
Depth |
21 3/8in/54.3cm | ||||
|
Height |
19 3/8in/49.3cm | ||||
|
Model | |||||
|
Capacity |
2KVA/1.4kW | ||||
|
Input | |||||
|
Voltage |
120V or 220V Input Requirement 30A@120V 16.2A@220V | ||||
|
Voltage Range |
120V -15%/+20% or 220V -15%/+20% | ||||
|
Frequency |
50Hz or 60Hz (400Hz available) | ||||
|
Phase |
Single | ||||
|
Output | |||||
|
Voltage |
120V ±20% | ||||
|
Voltage Regulation |
±1% | ||||
|
Frequency |
400Hz | ||||
|
Frequency Regulation |
±0.016Hz (Xtal oscillator) | ||||
|
Harmonic Distortion |
<3% at 100% linear load | ||||
|
Output Waveform |
Pure Sinewave | ||||
|
Output Current @.7pf |
120V-16.6A, 220V-9A | ||||
|
Non-linear Peak Current |
120V-24.6A, 220V-13.5A for 30 sec. | ||||
|
Power Factor |
0.7 | ||||
|
Efficiency | |||||
|
AC to AC |
>85% | ||||
|
Overload Capacity |
110% continuous,110-150% load 30 seconds, over 150% causes unit to shut down. Auto restart upon removal of the overload. | ||||
|
Short Circuit |
Unit will cut off and must be manually restarted | ||||
|
EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at 70dB | ||||
|
Over Temperature |
Inverter auto cut-off when heat sink temp over 80ºC | ||||
|
Audible Alarm | |||||
|
Overload |
Sounds continuously | ||||
|
Converter Fault |
Sounds continuously | ||||
|
Indicator | |||||
|
LCD |
Converter status, Input & Output voltage - frequency, loading % | ||||
|
LED |
| ||||
|
Environment | |||||
|
OperationTemp. |
-10-50%ºC; 14-122ºF | ||||
|
Relative Humidity |
20-90% non-condensing | ||||
|
Audible Noise |
Less than 45dB (at 1 meter) | ||||
|
Physical | |||||
|
Net Weight |
144lbs/64.8kg | ||||
|
Width |
7 1/8in/18.1cm | ||||
|
Depth |
21 3/8in/54.3cm | ||||
|
Height |
19 3/8in/49.35cm | ||||
1Specifications subject to change without notice.
|
Model | |||||
|
Capacity |
3KVA/2.1kW | ||||
|
Input | |||||
|
Voltage |
120 or 220V Input Requirement 45A@120V 25A@220V | ||||
|
Voltage Range |
120V -15%/+20% or 220V -15%/+20% | ||||
|
Frequency |
50Hz or 60Hz (400Hz available) | ||||
|
Phase |
Single | ||||
|
Output | |||||
|
Voltage |
120 ±30% | ||||
|
Voltage Regulation |
±1% | ||||
|
Frequency |
400Hz | ||||
|
Frequency Regulation |
±0.016Hz (Xtal oscillator) | ||||
|
Harmonic Distortion |
<3% at 100% linear load | ||||
|
Output Waveform |
Pure Sinewave | ||||
|
Output Current @.7pf |
120V-25A | ||||
|
Non-linear Peak Current |
120V-37.6A
for 30 sec. | ||||
|
Power Factor |
0.7 | ||||
|
Efficiency | |||||
|
AC to AC |
>85% | ||||
|
Overload Capacity |
110% continuous,110-150% load 30 seconds, over 150% causes unit to shut down. Auto restart upon removal of the overload. | ||||
|
Short Circuit |
Unit will cut off and must be manually restarted | ||||
|
EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at 70dB | ||||
|
Over Temperature |
Inverter auto cut-off when heat sink temp over 80ºC | ||||
|
Audible Alarm | |||||
|
Overload |
Sounds continuously | ||||
|
Converter Fault |
Sounds continuously | ||||
|
Indicator | |||||
|
LCD |
Converter status, Input & Output voltage - frequency, loading % | ||||
|
LED |
| ||||
|
Environment | |||||
|
OperationTemp. |
-10-50%ºC; 14-122ºF | ||||
|
Relative Humidity |
20-90% non-condensing | ||||
|
Audible Noise |
Less than 45dB (at 1 meter) | ||||
|
Physical | |||||
|
Net Weight |
144lbs/64.8kg | ||||
|
Width |
7 1/8in/18.1cm | ||||
|
Depth |
21 3/8in/54.3cm | ||||
|
Height |
19 3/8in/49.35cm | ||||
1Specifications subject to change without notice.