1KVA Solid State Frequency Converter Specifications |
|||||
|
Model |
1KSS6050/5060 | ||||
|
Capacity |
1KVA/700W | ||||
|
Input | |||||
|
Voltage |
120 or 220V | ||||
|
Voltage Range |
120V-15%/+20% or 220V-15%/+20% | ||||
|
Current |
220V - 5.2A @ Full Load (7.8A @ Current limit) | ||||
|
120V - 9.6A @ Full Load (14.3A @ Current limit) | |||||
|
Frequency |
Any Frequency from 45 65 hz (specify if 400hz) | ||||
|
Phase |
Single | ||||
|
Output | |||||
|
Voltage |
120 or 220Vac ±20% Adjustable from nominal | ||||
|
Voltage Regulation |
±1% From setpoint | ||||
|
Frequency |
50Hz or 60Hz (Switch selectable) (400 Hz available) | ||||
|
Frequency Regulation |
±.0005 Hz | ||||
|
Harmonic Distortion |
< 3% at 100% Linear Load | ||||
|
Output Waveform |
Pure Sinewave | ||||
|
Output Current @ .7pf |
220V - 4.5A | ||||
|
120V - 8.3A | |||||
|
Non-Linear Peak |
220V - 6.8A | ||||
|
120V - 12.5A | |||||
|
Power Factor |
0.7 | ||||
|
Efficiency |
| ||||
|
AC to AC |
>85% | ||||
|
Protection |
| ||||
|
Overload Capacity |
105% continuous, over 105% causes unit to shut down. Auto restart upon removal of overload. | ||||
|
Short Circuit |
Unit will cut out and must be manually restarted | ||||
|
EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at 70dB (EN 50091-2 CE approved) | ||||
|
Over Temperature |
Inverter auto cut-off when heat sink temp. over 80° C | ||||
|
Audible Alarm |
| ||||
|
Overload |
Sounds continuously | ||||
|
Converter Fault |
Sounds continuously | ||||
|
Indicator |
| ||||
|
LCD |
Converter status, INPUT & OUTPUT voltage-frequency, loading % | ||||
|
LED |
| ||||
|
Environment |
| ||||
|
Operation Temp. |
-10 to 50° C; 14-122° F | ||||
|
Relative Humidity |
20-90% non-condensing | ||||
|
Audible Noise |
< 45dB @ 3 ft. | ||||
|
Physical |
| ||||
|
Net Weight |
67.5lbs/30.7kg | ||||
|
Dimension |
| ||||
|
Depth |
16in/ 40.6cm | ||||
|
Width |
7.1in/ 18cm | ||||
|
Height |
12.1in/ 30.73cm | ||||
Specifications subject to change without notice.