1KVA Solid StateFrequency Converter Specifications 400Hz
 

Model

1KSS60400/50400

Capacity

1KVA/700W

Input

Voltage

120V or 220V *see note

Voltage Range

120V -15%/+20% or 220V -15%/+20%

Current
Requirement

220V - 5.2A @ Full Load (7.8A @ Current limit)

120V - 9.6A @ Full Load (14.3A @ Current limit)

Frequency

50Hz or 60Hz

Phase

Single

Output

Voltage

120V (Locked)

Voltage Regulation

±1%

Frequency

400Hz
(50/60hz available)

Frequency Regulation

±0.016Hz (Xtal oscillator)

Harmonic Distortion

<3% at 100% linear load

Output Waveform

Pure Sinewave

Output Current @ .7pf

220V - 4.5A

120V - 8.3A

Non-Linear Peak
Current for 30 sec.

220V - 6.8A

120V - 12.5A

Power Factor

0.9

Efficiency

AC to AC

>85%

Overload Capacity

110% continuous,110-150% load 30 seconds, over 150% causes unit to shut down. Auto restart upon removal of the overload.

Short Circuit

Unit will cut off and must be manually restarted

EMI Filter

10-100KHz at 40dB, 100KHz-100MHz at 70dB

Over Temperature

Inverter auto cut-off when heat sink temp over 80ºC

Audible Alarm

Overload

Sounds continuously

Converter Fault

Sounds continuously

Indicator

LCD

Converter status, Input & Output voltage - frequency, loading %

LED

Line: Green LED

Inverter: Green LED

Fault: Red LED

Overload: Yellow LED

Environment

OperationTemp.

-10-50%ºC; 14-122ºF

Relative Humidity

20-90% non-condensing

Audible Noise

Less than 45dB (at 1 meter)

Physical

Net Weight

67.5lbs/30.7kg

Width

7 1/8in/18.1cm

Depth

16in/40.6cm

Height

19 3/8in/49.3cm

Note: Input voltages of 208V single phase (phase-to-phase on a 3-phase 120/208V line)- with 2 hot lines and 240V single phase (from a 120/20V split-phase source) - 2 hot lines are both acceptable with one hot on the input N ternimal, and another hot on the L2 input terminal.

1Specifications subject to change without notice.

 

 